Battery state of health, or SoH, describes how a battery’s capability compares with a defined baseline. State of charge, or SoC, describes its current charge level. A fully charged battery can still have reduced capacity. For stationary solar storage, the useful question is whether the battery can still deliver the energy and power the site requires under agreed conditions. A dashboard percentage is an estimate until you know the definition, reference and conditions behind it.
Read the two percentages separately
Suppose a battery could originally deliver 100 Ah within the manufacturer’s permitted test window, and the same protocol now measures 82 Ah. On that basis its capacity SoH is 82%. If the battery’s SoC estimate represents the fraction of its present usable charge in that same window, reaching 100% SoC would mean it is at the top of that window. Its usable charge would still be about 82 Ah. Displays may map reserved capacity differently, so this arithmetic is an illustration rather than a way to decode every BMS.
If the display shows 50% SoC under that simplified definition, about 41 Ah remain in the defined window. Ah is a measure of electric charge. It does not directly represent AC energy available to a site. That calculation needs voltage over the discharge, or measured DC energy, plus the losses and consumption between the battery and the supported loads.

The research paper on state of energy and state of charge separates stored charge from the energy a battery can actually deliver. For reserve settings rather than capacity decline, see depth of discharge and backup reserve.
Battery health can mean capacity, energy or power
Capacity retention compares measured charge in Ah with the initial or rated Ah under a documented procedure. This is useful when comparing how far a battery can discharge within a specified window.
Energy retention compares watt-hours or kilowatt-hours at a defined metering point. A well-defined DC energy test can help isolate battery capability. An AC test at a declared boundary can help answer what the site receives. The two tests cannot be compared directly if one includes inverter and auxiliary losses and the other does not.
Power capability answers whether the battery can support a load at a specified rate, temperature and SoC without reaching an operating limit. A pack may still deliver sufficient energy at light load but shut down earlier under a larger load. An increase in resistance can contribute to higher voltage drop and heating under current, but the pack, connections, controller and load also need to be evaluated. Avoid substituting a single resistance number for a documented power test.
Consider a separate hypothetical pack that originally delivered 10.0 kWh DC under a defined protocol. It now delivers 8.4 kWh DC under the same conditions, equivalent to 84% energy retention. If the load-side boundary receives 7.6 kWh AC during that later test, 7.6 kWh is the useful result for that boundary. Comparing 7.6 kWh AC with the original 10.0 kWh DC would mix aging with conversion and auxiliary losses. For a deeper treatment of meter placement, refer to the battery round-trip efficiency guide.

Why a battery can appear to lose capacity overnight
Start by checking what changed between the two observations. A new backup reserve reduces the discharge window available to loads. A controller update can change the mapping between displayed SoC and the permitted range. A higher demand can reach voltage or current limits earlier. Different temperatures can change the observed result. None of these alone establishes irreversible degradation.
Use the solar battery monitoring guide to assemble the time series: SoC, battery current, battery voltage, temperature, load and fault events. Note the configured reserve and whether the site changed its operating schedule. Compare sustained trends with single readings. If the inverter and BMS disagree, record both screens and confirm which sensor and resolution each value uses.
An apparent drop can also arise when the estimate has drifted. Many battery systems integrate measured current, and measurement offsets or gaps over time can affect that estimate. LiFePO4 has a relatively flat voltage range over part of its operation, so a single voltage reading under load is especially poor evidence of usable capacity. A reset can alter the displayed value without restoring energy. Only use recalibration or service functions described by the manufacturer.
In a multi-module cabinet, ask whether the displayed health number describes one module, the average of several modules, or the capability of the whole cabinet. An average can hide a module that reaches its permitted voltage or temperature limit early. Export the individual readings where the approved software provides them, and preserve the event timestamps. Comparing a cabinet average today with a single module’s commissioning value can generate a false conclusion even when both readings are individually valid.
Plan a fair assessment for a stationary pack
- Record the battery model, serial numbers, configuration, firmware and original acceptance result. Ask whether the baseline was rated capacity, factory measured capacity or installed usable energy.
- Record the test boundary, permitted starting and ending conditions, temperature, load profile and data sampling. Compare like with like, including which equipment and auxiliaries are counted.
- Ask a qualified service provider to confirm the approved procedure and limits. Arrange continuity for critical loads before any planned test. Avoid forcing deep discharge, overriding protective limits or opening battery enclosures.
- Keep the raw report, energy or charge readings and event log together. Take note of alarms and interruptions that could invalidate the comparison.
- Compare the verified result with the site’s required usable energy and peak power, then review the warranty terms and the agreed acceptance criteria.

For a commercial backup site, compare capability at the actual discharge demand rather than only on a quiet weekend. At a constant supported load of 2 kW, the earlier numerical example’s 7.6 kWh of measured AC energy would correspond to 3.8 hours if the same conditions and boundary applied and power remained within limits. This is an arithmetic illustration. Actual backup time changes with the load profile, reserve, temperature and available power.
When to escalate, and what to send
A decreasing health estimate with stable service may call for trend tracking and a documented check. Repeated protection events, physical damage or signs of overheating require a qualified response under the site and manufacturer safety procedures. Those findings should not be managed by altering a reserve or changing a software limit to get a better number.
For a warranty discussion, collect the agreed reference, test conditions and logs before deciding that a claim threshold has been met. There is no universal replacement percentage that applies to every battery deployment. A pack may no longer meet one site’s required energy while remaining adequate elsewhere, and a warranty criterion may use a different metric from the business requirement. See how to read LiFePO4 lifespan and warranty terms for the documents to request.
If you need a project review, send GINZA Power the battery model, existing baseline and recent logs. Include the loads you must support and the required backup duration so an engineer can evaluate the observed result in context.
Sources and interpretation
- Research on the state of energy of lithium-ion batteries explains why remaining charge and usable energy diverge.
- Performance and health test procedure for grid energy storage systems illustrates why storage metrics should be measured at a defined system boundary and under stated conditions. Test procedures for a particular installation must be agreed with the equipment provider.