kW measures active power, while kVA measures apparent power. Their relationship is the load’s power factor: kW = kVA × power factor. When selecting inverter or PCS output for commercial solar backup, check both the active-power limit and the apparent-power or current limit.
A battery’s kWh rating answers a different question about stored energy. A large energy cabinet does not automatically have enough output capability for a particular motor, mixed load or starting event. This guide explains the power comparison before linking it to a separate runtime calculation.
Quick answer: convert using the measured power factor
If a load requires 8 kW at a true power factor of 0.8, its apparent demand is 8 ÷ 0.8 = 10 kVA. A hypothetical output rated at both 10 kW and 10 kVA could meet those two steady-state numerical limits, subject to its operating envelope and the rest of the design.
Now increase that same example to 9 kW at a power factor of 0.8. Apparent demand becomes 11.25 kVA. It exceeds the hypothetical 10 kVA limit even though 9 kW is below the 10 kW active-power limit. Passing the kW comparison alone would miss the constraint.
The Schneider Electrical Installation Guide defines power factor as active power divided by apparent power. Power factor is not the same quantity as conversion efficiency. Dividing load energy by 0.8 does not automatically estimate battery losses.

Compare both steady-state output numbers
| Active demand at power factor 0.8 | Required apparent power | 10 kW / 10 kVA comparison |
|---|---|---|
| 8 kW | 10 kVA | Within both numerical limits |
| 9 kW | 11.25 kVA | Exceeds 10 kVA |
Equality with a nameplate limit is not a complete site acceptance. The permitted operating envelope, ambient derating, phase allocation, starting duty and required design allowances still need review. The table isolates the two steady-state comparisons so a passing kW total cannot hide a failing kVA result.
Read the output specification beyond the headline number
| Required information | What to establish |
|---|---|
| Continuous active output | kW available in the required operating mode |
| Apparent output or current | kVA or current envelope at the specified voltage |
| Leading and lagging loads | Permitted power-factor range and any derating |
| Starting and overload duty | Magnitude, duration and allowed repetition |
| Site conditions | Temperature, altitude and configuration effects |
| DC supply | Battery voltage and permitted discharge capability |
Confirm whether the figures apply to grid-connected operation, islanded backup or a particular output port. A hybrid inverter’s export specification does not necessarily describe its backup port. Keep the accepted operating mode on the load schedule and quotation.
A commercial ESS energy label may describe nominal battery capacity while the PCS is configured or supplied separately. Identify the exact PCS rating and architecture for the commercial storage option. Do not infer it from the cabinet’s kWh number or from another product in the family.
Use true power factor for loads with distortion
In a simple sinusoidal case, displacement power factor can be represented by the cosine of the voltage-current phase angle. With distorted currents, that phase-angle value alone may not describe the total apparent demand. The Schneider harmonic-distortion reference distinguishes the two measures.
Ask the electrician for suitably measured kW, kVA, current and true power factor over representative operation. Record the instrument, measurement boundary and interval. A single nameplate value or a short low-load observation may not represent the combined site at its relevant duty.
For mixed loads, do not simply average the individual power-factor labels. The aggregate demand depends on simultaneous active and reactive behavior, waveform distortion and phase loading. A measured operating profile and an engineer’s model give a more defensible starting point.

Starting duty needs its own check
A motor can require a different current and apparent power during starting than during established operation. Record the motor, starter type, starting duration, simultaneous loads and permitted voltage behavior. The inverter or PCS overload specification must address the actual event, not only a steady-state multiplication.
A soft starter or variable-frequency drive can change the requirement, but the installed combination still needs assessment. Do not assume that any device described as a drive removes every starting or harmonic issue. Retain the equipment-specific evidence and the qualified provider’s acceptance criteria.
Use the pump backup planning guide for pumping duty and start information. It complements the apparent-power calculation without replacing the output-envelope review.
Calculate runtime after power capability is established
Suppose an illustrative load consumes a steady 8 kW for two hours. Its AC energy requirement is 16 kWh. Battery energy must then account for the permitted operating window, conversion losses, auxiliary consumption and reserve according to the project design. The power factor is already reflected in the output and current assessment; it is not an extra 20 percent energy-loss factor.
The commercial runtime worksheet separates usable energy and PCS power. Use that distinction when reading an offer: one system may have enough energy for two hours but lack the necessary apparent output or starting capability.
A time-varying process should use its measured kW schedule rather than the peak multiplied by every hour. Keep the chosen backup duties, expected interruptions and replenishment conditions visible so an energy calculation supports the operating objective.

Review phases and operating constraints together
For three-phase equipment, total power does not by itself show whether each phase can support its assigned loads. A large single-phase load can encounter a per-phase constraint even when the total looks acceptable. Review the manufacturer’s unbalanced-load capability and the phase schedule.
The three-phase backup guide covers that allocation. Schneider’s kVA calculation reference provides a separate explanation of voltage and current relationships. Its transformer discussion does not establish an inverter’s allowable operating envelope.
Prepare a load file a supplier can evaluate
For each essential process, record measured input kW, kVA or true power factor, phase, start behavior and operating hours. Include the simultaneous combination the customer expects during backup. Identify loads that can be shed and those that must continue without an interruption beyond their allowed tolerance.
Ask the supplier to respond against a named inverter or PCS, battery arrangement and site condition. Keep unresolved starting or waveform questions as open engineering items. A quote should not turn them into assumed compatibility simply because the steady-state kW total fits.
Identify whether a motor label shows shaft output or electrical input
A motor’s stated mechanical output is not automatically its electrical input demand. If an illustrative motor delivers 4 kW mechanically at an assumed 90 percent efficiency, the electrical active input would be about 4.44 kW before considering its power factor. At an assumed 0.8 power factor, the steady apparent input would be about 5.56 kVA. Starting duty remains a separate check.
These invented values show why motor efficiency and power factor belong in different fields. Ask the provider which quantity each nameplate or measurement represents before summing the backup loads.
Sources and interpretation
The electrical references establish active and apparent power and the distinction between total and displacement power factor. Numerical loads and output ratings are invented. They do not identify a GINZA PCS configuration or replace professional waveform, phase and starting assessment.
- Schneider Electrical Installation Guide: power factor definition
- Schneider: total versus displacement power factor
- Schneider: kVA, current and kW calculation reference
Frequently asked questions
Is a 10 kVA inverter always a 10 kW inverter?
No universal conversion applies without the active-power rating and the load’s power factor. Check both output limits, their conditions and the actual operating mode.
Does poor power factor reduce the battery’s kWh label?
The stored-energy label does not change by that arithmetic. Power factor changes apparent demand and current for a given active load; actual system losses and operating limits must be assessed separately.
What should a commercial enquiry include?
Send the country, load profile, measured power information, phase and starting requirements, backup duration and proposed PCS through the GINZA commercial enquiry. Request an equipment-specific response.